Mersen A6D30R

Mersen AMP-TRAP® 2000 SmartSpot® A6D30R Current Limiting Low Voltage North American Time Delay Power Fuse, 30 A, 600 VAC, 200 kA Interrupt, RK1 Class, Cylindrical Body

  • MPN: A6D30R

  • IESPN: 44594

  • UPC: 782001991869

  • Min Order Qty: 1

  • Quantity Interval: 1

  • Sold as: EACH
    • Availability: loading

    • Branch Availability
Mersen A6D30R

Amp-Trap 2000® time-delay A6D-R fuses provide IEC Type 2 "no damage" protection to existing mains, feeders, and branch circuits serving motor and non-motor loads. A6D-R fuses will open fast enough under extreme fault conditions for maximum short circuit protection to prevent damage to motor starters, switches, and other circuit components, yet also provide the time-delay needed for motor in-rush currents. A6D-R fuses can be used to replace older 600V Class H, K or RK5 fuses already installed in the field.

Mersen AMP-TRAP® 2000 SmartSpot® Power Fuse, Current Limiting Low Voltage North American Time Delay, Series: A6D-R, Indicating, Rejection, 30 A, 600 VAC, 200 kA Interrupt, Class: RK1, Ferrule Terminal, Clip Mounting, Cylindrical Body, Dual Element, Fiberglass, 13/16 in Dia x 5 in L Body

Type      Current Limiting Low Voltage North American Time Delay
Series      A6D-R
Indicating/Non-Indicating      Indicating
Rejection/Non-Rejection      Rejection
Amperage Rating      30 A
Voltage Rating      600 VAC
Interrupt Rating      200 kA
Class      RK1
Terminal Type      Ferrule
Mounting Type      Clip
Body Type      Cylindrical
Element      Dual
Material      Fiberglass
Body Size      13/16 in Dia x 5 in L
  • Solid state SmartSpot® indicator
  • Time delay for motor starting and transformer inrush currents without nuisance opening
  • 300 kA interrupting rating, self certified (UL witnessed)
  • Extremely current limiting for low peak let-thru current
  • Easy 2-to-1 selectivity for prevention of nuisance shutdowns and "blackouts"
  • Rejection style design prevents replacement errors (when used with recommended fuse blocks)
  • High visibility orange label gives instant recognition
  • Reduced inventory by taking the place of class RK5, K and H fuses
  • Metal embossed date and catalog number for easier traceability and lasting identification
  • Fiberglass body provides dimensional stability in harsh industrial settings
  • High grade silica filler ensures fast arc quenching
  • Recommended for arc flash energy reduction
  • A6D-R fuses will open fast enough under extreme fault conditions for maximum short
  • Plated terminals
  • Arc flash mitigating
  • Tin-plated copper contact