GE SPUV012DCR

GE SPUV012DCR Field Installed Undervoltage Release Module, 12 VDC

  • MPN: SPUV012DCR

  • IESPN: 5785

  • UPC: 783164072570

  • Min Order Qty: 1

  • Quantity Interval: 1

  • Sold as: EACH
    • Availability: loading

    • Branch Availability
GE SPUV012DCR

The undervoltage release is an electronic module used to open the circuit breaker when the monitored voltage drops below 35 to 60% of its rated value. The undervoltage release resets when the monitored voltage is re-established allowing the circuit breaker to reclose (the sealing voltage of the UVR is 60 to 85% of its rated voltage). An undervoltage release trip operation is produced by the MicroVersaTrip Plus™ unit in response to a signal from the undervoltage release module. This allows the trip unit to record, display, distinguish an d comm un icate (in MicroVersaTrip PM™ trip units) that the breaker opening event was due to undervoltage release. Operation of the undervoltage release module will prevent breaker contact closure, i.e. kiss-free operation. When energized, the undervoltage release supplies 24 VDC power to the trip unit to power the display.

GE Undervoltage Release Module, Field Installed, 12 VDC, For Use With: Power Break® II and Insulated Case Circuit Breaker

Type      Field Installed
Voltage Rating      12 VDC
Suitable For Use With      Power Break® II and Insulated Case Circuit Breaker